MHY 734.031
Base
The MHY 734.031 base is intended for connection with automatic fire detector LITES to control other equipment, eg fire shutter.
Description
Technical parameters
Working conditions
Documents and certificates
The MHY 734.031 base is intended for connection with automatic fire detector LITES to control other equipment, eg fire shutter.
The base is supplied with 24 V. AC or DC voltage. The voltage is rectified and stabilized to supply the detector. If the detector is activated to the alarm state, the relay closes in the socket. The independent changeover contact of the relay can be used to control eg a fire shutter. The reset is performed by disconnecting the power supply.
Technical parameters | |
---|---|
Supply voltage | 24V DC, AC ± 15 % |
Self-consumption | |
idle state | max. 5 mA |
alarm status | max. 50 mA (including detector) |
Connectable detectors | MHG 231.070, MHG 331.071 |
Relay contact | |
current | max.1 A |
voltage | max. 60 Vss / 30 Vst |
Reset - resetting the base | power stop for min. 2 s |
Cross section of connectable wires | 0,2 ÷ 1,5 mm² |
Coverage according to ČSN EN 60529 | IP 43 - location on the ceiling, IP 40 - another place |
Dimensions | ø98 × 28 mm |
Working conditions | |
---|---|
The base for fire shutters MHY 734.031 is designed for indoor areas of buildings without the presence of aggressive substances and wherever it meets its coverage and climate resistance and where there is no sudden temperature change leading to dew and icing. | |
Operating temperature range | -25°C to +70°C |
Relative air humidity | max. 95% for +40°C |
Atmospheric pressure | 86 to 106 kPa |