MHY 924 is addressable module intended for power and control of alarm sirens, beacons, sirens with beacons connected to the detection line of addressable C.I.E. LITES.

MHY 924 is addressable module intended for power and control of alarm sirens, beacons, sirens with beacons connected to the detection line of addressable C.I.E. LITES. Printed circuit board can be installed directly to the mounting base of sirens ROSHNI ROLP, ROLPSB. MHY 924 is connected to the detection line of addressable C.I.E. MHU 109, MHU 110/111, MHU 115, MHU 116, MHU 117:
  • Two wire – siren is powered from internal ACCU (fig.1)
  • Four wire – siren is powered from C.I.E., eventually from external source (fig.2)
Conditions for activation of module output, and time of its activation are defined in configuration program of individual C.I.E., to which is module connected. Address is set using addressable Principle of operation Module MHY 924 is powered by pulse voltage from detection line of C.I.E: It contains source for powering of own electronic circuits and circuit for control of siren. It also contains changer of voltage for siren 19 ÷ 22 V from range of input voltage 8 ÷ 28 V (ACCU 9 V or external power 8 ÷ 28 V). An output for siren is activated, when defined conditions are met.