MHG 943
Fourfold input element (technological detector)
MHG 943 is an addressable input element with four inputs intended in cooperation with addressable C.I.Es Lites
MHG 943 is an addressable input element with four inputs intended in cooperation with addressable C.I.Es Lites for automatic signalling of user defined exceptional state(s) of anyexternal device, which indicates this state either by closing or opening an electrical contact or by voltage received on the optoisolated input. Contacts can also be set as guarded.
The element communicates with C.I.E. on 4 consecutive addresses. The first one is set by the addressing preparation MHY 535. Activation of any input is signalled by blinking of a red LED and additional SMD LED of appropriate input. The element consists of printed circuit board with terminal blocks which is placed in a plastic box with removable transparent cover.
The element is powered by a pulse voltage from the detection line of C.I.E. It contains power supply for its own electronic circuits. Evaluation circuits of input can be set as optoisolated or for connection of switching contact. These inputs can as well be set as guarded, where with the external device an opening (FAULT) or closing (ALARM) contacts can be connectedsimultaneously. At the same time the loop is guarded for interruption or a short-circuit.
Addressable part registers the communication from C.I.E., refers under appropriate address and sends information about input activation to the C.I.E.
Technical parameters | |
---|---|
Power supply | (18 to 21) Vimp |
Rated voltage | 12 Vimp |
Standby current | max. 200 μA |
Number of inputs | 4 |
Optoisolated input – current | |
input voltage | 9 V ÷ 30 V (logical 1), 0 V ÷ 3 V (logical 0) |
input resistance | cca 10 kΩ |
Input contact closing/opening | |
resistance of line and closed contact | max. 1 kΩ |
resistance of open contact | min. 10 kΩ |
output test voltage | cca 12 Vimp |
output test current (closed contact) | max. 1,2 mA |
Input contact guarded | |
Test voltage | 12 Vimp |
Line resistance | max. 100 Ω |
test current standby | cca 0,8 mAimp |
test current FIRE | cca 1,5 mAimp |
test current FAULT | cca 0,5 mAimp |
resistance standby | 10 kΩ |
resistance FIRE | 4,7 kΩ |
resistance FAULT | 20 kΩ |
Optical signalling | red LED |
Address range (by indicating preparation MHY 535) | 1 – 128 |
Parallel signalling line resistance | max. 100 Ω |
Protection according to ČSN EN 60529 | IP 65 |
Radio screening degree according to ČSN EN 55022 | B-class equipment |
Cross-section of connectable wires | (0,2 ÷ 1,5) mm² |
Dimensions (w × h × d) | (130 × 941 × 57) mm |
Weight | cca 220 g |
Hlásič je určen k provozu se zařízením bezpečným ve smyslu ČSN EN 60950.
Working conditions | |
---|---|
Application of the detector is in areas protected against weather conditions with classification according to ČSN EN 60721-3-3. | |
K: climatic conditions for environment | 3K5 |
working temperature range | (-25 to +70) °C |
max. relative humidity | max. 95 % at +40 °C |
atmospheric pressure range | (86 až 106) kPa |
without condensation and ice accretion | |
Z: special conditions | 3Z1 heat radiation negligible |
B: biological conditions | 3B1 without presence of flora and fauna |
C: chemical active substances | 3C1 |
S: mechanical active substances | 3S1 |
M: mechanical conditions | 3M1 |
Duration of significant temperature (45°C ÷ 70°C) | 2 months/year |
Duration of significant humidity (85 % ÷ 95 % / ≤ 40°C) | 100 hours/year |