MHG 362

Heat Detector

The MHG 361 Heat Detector is a self-acting detector intended for the automatic fire alarm signalling as a heat detector of the analog and addressable Electric Fire Detection and Alarm System LITES.

The MHG 361 Heat Detector is a self-acting detector intended for the automatic fire alarm signalling as a heat detector of the analog and addressable Electric Fire Detection and Alarm System LITES. It responds to a fixed reached temperature level or to a temperature change before or during a fire.

The MHG 361 MHG 362 detector is meant for cooperation with the analog Control and Indicating Equipments (C.I.E.) MHU 110, MHU 111, MHU 115, MHU 116, MHU 117, eventually with theaddressable C.I.E. MHU 109. The detector contains a program that evaluates the fire situation pursuant to measuring of surrounding temperature, namely in agreement with the followingadjustable characteristics:

 

  • the threshold temperature - at this temperature level the fire alert puts on; it can be set in the interval 45°C - 90°C at 3°C
  • the temperature change that leads to an alert (so-called differencial part); it may be set in the interval 10°C - 45°C at 5°C; eventually the reactio n to the temperature change may be not allowed
  • the minimum average speed (steepness) of the temperature increase so that it comes to a respond to the differencial part, if it`s allowed; it may be set at c. 3°C/min or 10°C/min
  • the minimum temperature that must be reached at a fire alert and also at the reaction of the differencial part; it can be set from 0°C up to the threshold temperature in seven equidistant steps

 

Further the pre-alert in the interval between 3°C a nd 24°C before the alert can be adjusted (applies only for the C.I.E.`s MHU 110 and MHU 111). If the evaluated temperatures are too low,too high, or they do not make sense, the detector signals a fault.

The adjustable characteristics can be set either into the configuration program and recorded to the detector through the C.I.E. (MHU 110 or MHU 111), or they can be programmed right bymeans of the preparation MHY 535 (MHU 109).

The detector is to install into the MHY 734 Base, or into the Base MHY 734.028 with audible signalling, at the installation it is possible to use the Mounting Bar Stock MHY 736.
The detectors comply with the standard specifications ČSN EN 54-5. For its use in the Electric Fire Detection and Alarm System it is liable to the compliance examination according to law No. 22/1997 Sb., in wording law No. 71/2000 Sb. and the relevant orders of the government.